What size wire for 175 amps?

Advertisement
2/0 AWG copper

minimum for 175 A (75 °C column, NEC 310.16) · 4/0 AWG aluminum

175 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft2/0 AWG2/0 AWG
50 ft2/0 AWG2/0 AWG
75 ft2/0 AWG2/0 AWG
100 ft2/0 AWG2/0 AWG
125 ft3/0 AWG2/0 AWG
150 ft4/0 AWG2/0 AWG
200 ft300 kcmil2/0 AWG
250 ft350 kcmil3/0 AWG
300 ft400 kcmil4/0 AWG

Load assumed at the full 175 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 140 A continuous load on a 175 A breaker).

Check your exact run

FAQ

What size wire for a 175 amp circuit?

2/0 AWG copper or 4/0 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 2/0 AWG on a 175 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.

Other circuit sizes