Wire Size Calculator

Find the right copper or aluminum wire gauge (AWG/kcmil) for your amps, run length and voltage, checking NEC ampacity and keeping voltage drop under 3%.

Advertisement

How to use it

  1. Enter the load in amps (for continuous loads such as EV chargers or heaters, choose "Yes" to size at 125%).
  2. Enter the one-way distance from the panel to the load.
  3. Pick the voltage and conductor material; 3% is the common voltage-drop target for branch circuits.

How it works

The calculator picks the smallest wire whose 75 °C ampacity (NEC Table 310.16) covers the load, applies the small-conductor limits of 240.4(D) (14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A copper), then increases the size until voltage drop = 2 × length × amps × resistance per foot stays under your limit.

Many residential terminals and NM (Romex) cable are limited to the 60 °C column; check the cable type and equipment labels.

FAQ

What size wire for 30 amps?

10 AWG copper for a typical 30 A circuit; long runs may need 8 AWG to keep voltage drop under 3%.

Does distance change wire size?

Yes. Ampacity sets the minimum size; on long runs voltage drop usually forces a larger wire.