10 AWG copper

minimum for 30 A (75 °C column, NEC 310.16) · 8 AWG aluminum · typical for electric dryers and water heaters

30 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft10 AWG10 AWG
50 ft8 AWG10 AWG
75 ft8 AWG10 AWG
100 ft6 AWG8 AWG
125 ft4 AWG8 AWG
150 ft4 AWG8 AWG
200 ft3 AWG6 AWG
250 ft2 AWG4 AWG
300 ft2 AWG4 AWG

Load assumed at the full 30 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 24 A continuous load on a 30 A breaker).

Check your exact run

FAQ

What size wire for a 30 amp circuit?

10 AWG copper or 8 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 10 AWG on a 30 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.