What size wire for 45 amps?

Advertisement
8 AWG copper

minimum for 45 A (75 °C column, NEC 310.16) · 6 AWG aluminum

45 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft8 AWG8 AWG
50 ft8 AWG8 AWG
75 ft6 AWG8 AWG
100 ft4 AWG8 AWG
125 ft4 AWG6 AWG
150 ft3 AWG6 AWG
200 ft2 AWG4 AWG
250 ft1 AWG4 AWG
300 ft1/0 AWG3 AWG

Load assumed at the full 45 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 36 A continuous load on a 45 A breaker).

Check your exact run

FAQ

What size wire for a 45 amp circuit?

8 AWG copper or 6 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 8 AWG on a 45 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.