Wire size for 175 amps at 300 feet

Advertisement

175 A at 300 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper400 kcmil3.37 V (2.81%)
120 VAluminum>600 kcmil–
240 VCopper4/0 AWG6.38 V (2.66%)
240 VAluminum350 kcmil6.35 V (2.65%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 175 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 175 amps at 300 feet?

At 240 V: 4/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances