What size wire for 125 amps?

Advertisement
1 AWG copper

minimum for 125 A (75 °C column, NEC 310.16) · 2/0 AWG aluminum

125 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft1 AWG1 AWG
50 ft1 AWG1 AWG
75 ft1 AWG1 AWG
100 ft1/0 AWG1 AWG
125 ft2/0 AWG1 AWG
150 ft3/0 AWG1 AWG
200 ft4/0 AWG1/0 AWG
250 ft250 kcmil2/0 AWG
300 ft300 kcmil3/0 AWG

Load assumed at the full 125 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 100 A continuous load on a 125 A breaker).

Check your exact run

FAQ

What size wire for a 125 amp circuit?

1 AWG copper or 2/0 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 1 AWG on a 125 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.