Home › Wire size by amps › 150 amp

What size wire for 150 amps?

Advertisement
1/0 AWG copper

minimum for 150 A (75 °C column, NEC 310.16) · 3/0 AWG aluminum

150 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft1/0 AWG1/0 AWG
50 ft1/0 AWG1/0 AWG
75 ft1/0 AWG1/0 AWG
100 ft2/0 AWG1/0 AWG
125 ft3/0 AWG1/0 AWG
150 ft3/0 AWG1/0 AWG
200 ft250 kcmil2/0 AWG
250 ft300 kcmil3/0 AWG
300 ft350 kcmil3/0 AWG

Load assumed at the full 150 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 120 A continuous load on a 150 A breaker).

Check your exact run

FAQ

What size wire for a 150 amp circuit?

1/0 AWG copper or 3/0 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 1/0 AWG on a 150 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.