WireMath

Home › Wire size by amps › 175 amp › 250 ft

Wire size for 175 amps at 250 feet

Advertisement

175 A at 250 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper350 kcmil3.21 V (2.68%)
120 VAluminum600 kcmil3.09 V (2.57%)
240 VCopper3/0 AWG6.70 V (2.79%)
240 VAluminum300 kcmil6.19 V (2.58%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 175 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 175 amps at 250 feet?

At 240 V: 3/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath

Advertisement