Home › Wire size by amps › 175 amp › 125 ft

Wire size for 175 amps at 125 feet

Advertisement

175 A at 125 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper3/0 AWG3.35 V (2.79%)
120 VAluminum300 kcmil3.09 V (2.58%)
240 VCopper2/0 AWG4.23 V (1.76%)
240 VAluminum4/0 AWG4.38 V (1.82%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 175 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 175 amps at 125 feet?

At 240 V: 2/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances