What size wire for 60 amps?

Advertisement
6 AWG copper

minimum for 60 A (75 °C column, NEC 310.16) · 4 AWG aluminum · typical for EV chargers (48 A) and subpanels

60 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft6 AWG6 AWG
50 ft6 AWG6 AWG
75 ft4 AWG6 AWG
100 ft3 AWG6 AWG
125 ft2 AWG4 AWG
150 ft2 AWG4 AWG
200 ft1/0 AWG3 AWG
250 ft2/0 AWG2 AWG
300 ft2/0 AWG2 AWG

Load assumed at the full 60 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 48 A continuous load on a 60 A breaker).

Check your exact run

FAQ

What size wire for a 60 amp circuit?

6 AWG copper or 4 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 6 AWG on a 60 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.