What size wire for 250 amps?
Advertisement
250 kcmil copper
minimum for 250 A (75 °C column, NEC 310.16) · 350 kcmil aluminum
250 amp wire size by distance (3% voltage drop, copper)
| One-way distance | 120 V | 240 V |
|---|---|---|
| 25 ft | 250 kcmil | 250 kcmil |
| 50 ft | 250 kcmil | 250 kcmil |
| 75 ft | 250 kcmil | 250 kcmil |
| 100 ft | 250 kcmil | 250 kcmil |
| 125 ft | 250 kcmil | 250 kcmil |
| 150 ft | 300 kcmil | 250 kcmil |
| 200 ft | 400 kcmil | 250 kcmil |
| 250 ft | 500 kcmil | 250 kcmil |
| 300 ft | 600 kcmil | 300 kcmil |
Load assumed at the full 250 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 200 A continuous load on a 250 A breaker).
Check your exact run
FAQ
What size wire for a 250 amp circuit?
250 kcmil copper or 350 kcmil aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.
Can I use 250 kcmil on a 250 amp breaker for 150 feet?
Check voltage drop: see the distance table on this page.