What size wire for 15 amps?

Advertisement
14 AWG copper

minimum for 15 A (75 °C column, NEC 310.16) · 12 AWG aluminum · typical for lighting and general receptacle circuits

15 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft14 AWG14 AWG
50 ft12 AWG14 AWG
75 ft10 AWG14 AWG
100 ft8 AWG12 AWG
125 ft8 AWG10 AWG
150 ft8 AWG10 AWG
200 ft6 AWG8 AWG
250 ft4 AWG8 AWG
300 ft4 AWG8 AWG

Load assumed at the full 15 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 12 A continuous load on a 15 A breaker).

Check your exact run

FAQ

What size wire for a 15 amp circuit?

14 AWG copper or 12 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 14 AWG on a 15 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.