What size wire for 80 amps?
Advertisement
4 AWG copper
minimum for 80 A (75 °C column, NEC 310.16) · 2 AWG aluminum
80 amp wire size by distance (3% voltage drop, copper)
| One-way distance | 120 V | 240 V |
|---|---|---|
| 25 ft | 4 AWG | 4 AWG |
| 50 ft | 4 AWG | 4 AWG |
| 75 ft | 3 AWG | 4 AWG |
| 100 ft | 2 AWG | 4 AWG |
| 125 ft | 1 AWG | 4 AWG |
| 150 ft | 1/0 AWG | 3 AWG |
| 200 ft | 2/0 AWG | 2 AWG |
| 250 ft | 3/0 AWG | 1 AWG |
| 300 ft | 4/0 AWG | 1/0 AWG |
Load assumed at the full 80 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 64 A continuous load on a 80 A breaker).
Check your exact run
FAQ
What size wire for a 80 amp circuit?
4 AWG copper or 2 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.
Can I use 4 AWG on a 80 amp breaker for 150 feet?