Home › Wire size by amps › 20 amp

What size wire for 20 amps?

Advertisement
12 AWG copper

minimum for 20 A (75 °C column, NEC 310.16) · 10 AWG aluminum · typical for kitchen, bathroom and laundry receptacle circuits

20 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft12 AWG12 AWG
50 ft10 AWG12 AWG
75 ft8 AWG12 AWG
100 ft8 AWG10 AWG
125 ft6 AWG10 AWG
150 ft6 AWG8 AWG
200 ft4 AWG8 AWG
250 ft4 AWG6 AWG
300 ft3 AWG6 AWG

Load assumed at the full 20 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 16 A continuous load on a 20 A breaker).

Check your exact run

FAQ

What size wire for a 20 amp circuit?

12 AWG copper or 10 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 12 AWG on a 20 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.