What size wire for 20 amps?
Advertisement
12 AWG copper
minimum for 20 A (75 °C column, NEC 310.16) · 10 AWG aluminum · typical for kitchen, bathroom and laundry receptacle circuits
20 amp wire size by distance (3% voltage drop, copper)
| One-way distance | 120 V | 240 V |
|---|---|---|
| 25 ft | 12 AWG | 12 AWG |
| 50 ft | 10 AWG | 12 AWG |
| 75 ft | 8 AWG | 12 AWG |
| 100 ft | 8 AWG | 10 AWG |
| 125 ft | 6 AWG | 10 AWG |
| 150 ft | 6 AWG | 8 AWG |
| 200 ft | 4 AWG | 8 AWG |
| 250 ft | 4 AWG | 6 AWG |
| 300 ft | 3 AWG | 6 AWG |
Load assumed at the full 20 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 16 A continuous load on a 20 A breaker).
Check your exact run
FAQ
What size wire for a 20 amp circuit?
12 AWG copper or 10 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.
Can I use 12 AWG on a 20 amp breaker for 150 feet?
Check voltage drop: see the distance table on this page.