What size wire for 50 amps?

Advertisement
8 AWG copper

minimum for 50 A (75 °C column, NEC 310.16) · 6 AWG aluminum · typical for ranges, EV chargers and welders

50 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft8 AWG8 AWG
50 ft6 AWG8 AWG
75 ft4 AWG8 AWG
100 ft4 AWG6 AWG
125 ft3 AWG6 AWG
150 ft2 AWG4 AWG
200 ft1 AWG4 AWG
250 ft1/0 AWG3 AWG
300 ft2/0 AWG2 AWG

Load assumed at the full 50 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 40 A continuous load on a 50 A breaker).

Check your exact run

FAQ

What size wire for a 50 amp circuit?

8 AWG copper or 6 AWG aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 8 AWG on a 50 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.