What size wire for 200 amps?

Advertisement
3/0 AWG copper

minimum for 200 A (75 °C column, NEC 310.16) · 250 kcmil aluminum · typical for whole-house service

200 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft3/0 AWG3/0 AWG
50 ft3/0 AWG3/0 AWG
75 ft3/0 AWG3/0 AWG
100 ft3/0 AWG3/0 AWG
125 ft4/0 AWG3/0 AWG
150 ft250 kcmil3/0 AWG
200 ft300 kcmil3/0 AWG
250 ft400 kcmil4/0 AWG
300 ft500 kcmil250 kcmil

Load assumed at the full 200 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 160 A continuous load on a 200 A breaker).

Check your exact run

FAQ

What size wire for a 200 amp circuit?

3/0 AWG copper or 250 kcmil aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 3/0 AWG on a 200 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.