What size wire for 225 amps?

Advertisement
4/0 AWG copper

minimum for 225 A (75 °C column, NEC 310.16) · 300 kcmil aluminum

225 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft4/0 AWG4/0 AWG
50 ft4/0 AWG4/0 AWG
75 ft4/0 AWG4/0 AWG
100 ft4/0 AWG4/0 AWG
125 ft4/0 AWG4/0 AWG
150 ft250 kcmil4/0 AWG
200 ft350 kcmil4/0 AWG
250 ft500 kcmil4/0 AWG
300 ft500 kcmil250 kcmil

Load assumed at the full 225 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 180 A continuous load on a 225 A breaker).

Check your exact run

FAQ

What size wire for a 225 amp circuit?

4/0 AWG copper or 300 kcmil aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 4/0 AWG on a 225 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.