Wire Ampacity Chart

Wire ampacity chart for copper and aluminum conductors from 14 AWG to 600 kcmil at 60 °C, 75 °C and 90 °C, with resistance per 1,000 ft.

Advertisement
SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°CΩ/1000ft Cu
14 AWG152025–––3.07
12 AWG2025301520251.93
10 AWG3035402530351.21
8 AWG4050553540450.764
6 AWG5565754050550.491
4 AWG7085955565750.308
3 AWG851001156575850.245
2 AWG9511513075901000.194
1 AWG110130145851001150.154
1/0 AWG1251501701001201350.122
2/0 AWG1451751951151351500.0967
3/0 AWG1652002251301551750.0766
4/0 AWG1952302601501802050.0608
250 kcmil2152552901702052300.0515
300 kcmil2402853201952302600.0429
350 kcmil2603103502102502800.0367
400 kcmil2803353802252703050.0321
500 kcmil3203804302603103500.0258
600 kcmil3504204752853403850.0214

Not more than 3 current-carrying conductors in a raceway/cable, 30 °C ambient. Overcurrent protection for 14/12/10 AWG copper is limited to 15/20/30 A (NEC 240.4(D)).

How to use it

  1. Find your conductor size in the first column.
  2. Use the column matching the lowest temperature rating of the wire, terminals and equipment (usually 60 °C for ≤100 A / 14-1 AWG unless marked otherwise, 75 °C above).
  3. Apply derating for more conductors or hotter ambient.

How it works

Ampacity is the current a conductor can carry continuously without exceeding its insulation temperature rating. The 90 °C column is mainly used as the starting point for derating.

FAQ

How many amps can 12 gauge wire handle?

12 AWG copper is rated 20 A at 60 °C and 25 A at 75 °C, but the breaker is limited to 20 A.