What size wire for 300 amps?

Advertisement
350 kcmil copper

minimum for 300 A (75 °C column, NEC 310.16) · 500 kcmil aluminum

300 amp wire size by distance (3% voltage drop, copper)

One-way distance120 V240 V
25 ft350 kcmil350 kcmil
50 ft350 kcmil350 kcmil
75 ft350 kcmil350 kcmil
100 ft350 kcmil350 kcmil
125 ft350 kcmil350 kcmil
150 ft350 kcmil350 kcmil
200 ft500 kcmil350 kcmil
250 ft600 kcmil350 kcmil
300 ft>600 kcmil350 kcmil

Load assumed at the full 300 A. For continuous loads the circuit must be sized at 125% of the load (e.g. a 240 A continuous load on a 300 A breaker).

Check your exact run

FAQ

What size wire for a 300 amp circuit?

350 kcmil copper or 500 kcmil aluminum at 75 °C for short runs; longer runs need larger wire to limit voltage drop.

Can I use 350 kcmil on a 300 amp breaker for 150 feet?

Check voltage drop: see the distance table on this page.