50 A at 100 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper4 AWG3.08 V (2.57%)
120 VAluminum2 AWG3.19 V (2.66%)
240 VCopper6 AWG4.91 V (2.05%)
240 VAluminum4 AWG5.08 V (2.12%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 50 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 50 amps at 100 feet?

At 240 V: 6 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances