Wire size for 250 amps at 150 feet

Advertisement

250 A at 150 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper300 kcmil3.22 V (2.68%)
120 VAluminum500 kcmil3.18 V (2.65%)
240 VCopper250 kcmil3.86 V (1.61%)
240 VAluminum350 kcmil4.54 V (1.89%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 250 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 250 amps at 150 feet?

At 240 V: 250 kcmil copper keeps voltage drop under 3%. See the table for 120 V and aluminum.