Home › Wire size by amps › 250 amp › 50 ft

Wire size for 250 amps at 50 feet

Advertisement

250 A at 50 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper250 kcmil1.29 V (1.07%)
120 VAluminum350 kcmil1.51 V (1.26%)
240 VCopper250 kcmil1.29 V (0.54%)
240 VAluminum350 kcmil1.51 V (0.63%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 250 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 250 amps at 50 feet?

At 240 V: 250 kcmil copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances