225 A at 200 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper350 kcmil3.30 V (2.75%)
120 VAluminum600 kcmil3.18 V (2.65%)
240 VCopper4/0 AWG5.47 V (2.28%)
240 VAluminum300 kcmil6.36 V (2.65%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 225 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 225 amps at 200 feet?

At 240 V: 4/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances