225 A at 50 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper4/0 AWG1.37 V (1.14%)
120 VAluminum300 kcmil1.59 V (1.33%)
240 VCopper4/0 AWG1.37 V (0.57%)
240 VAluminum300 kcmil1.59 V (0.66%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 225 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 225 amps at 50 feet?

At 240 V: 4/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.