Wire size for 150 amps at 100 feet

Advertisement

150 A at 100 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper2/0 AWG2.90 V (2.42%)
120 VAluminum4/0 AWG3.00 V (2.50%)
240 VCopper1/0 AWG3.66 V (1.53%)
240 VAluminum3/0 AWG3.78 V (1.57%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 150 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 150 amps at 100 feet?

At 240 V: 1/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances