Wire size for 150 amps at 250 feet

Advertisement

150 A at 250 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper300 kcmil3.22 V (2.68%)
120 VAluminum500 kcmil3.18 V (2.65%)
240 VCopper3/0 AWG5.75 V (2.39%)
240 VAluminum250 kcmil6.35 V (2.65%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 150 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 150 amps at 250 feet?

At 240 V: 3/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances