15 A at 125 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper8 AWG2.87 V (2.39%)
120 VAluminum6 AWG3.03 V (2.52%)
240 VCopper10 AWG4.54 V (1.89%)
240 VAluminum8 AWG4.72 V (1.97%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 15 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 15 amps at 125 feet?

At 240 V: 10 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.