15 A at 50 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper12 AWG2.90 V (2.41%)
120 VAluminum10 AWG3.00 V (2.50%)
240 VCopper14 AWG4.61 V (1.92%)
240 VAluminum12 AWG4.77 V (1.99%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 15 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 15 amps at 50 feet?

At 240 V: 14 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances