WireMath

Home › Wire size by amps › 125 amp › 200 ft

Wire size for 125 amps at 200 feet

Advertisement

125 A at 200 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper4/0 AWG3.04 V (2.53%)
120 VAluminum300 kcmil3.54 V (2.95%)
240 VCopper1/0 AWG6.10 V (2.54%)
240 VAluminum3/0 AWG6.30 V (2.62%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 125 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 125 amps at 200 feet?

At 240 V: 1/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath