Wire size for 125 amps at 50 feet

Advertisement

125 A at 50 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper1 AWG1.93 V (1.60%)
120 VAluminum2/0 AWG1.99 V (1.66%)
240 VCopper1 AWG1.93 V (0.80%)
240 VAluminum2/0 AWG1.99 V (0.83%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 125 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 125 amps at 50 feet?

At 240 V: 1 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances