WireMath

Home › Wire size by amps › 45 amp › 200 ft

Wire size for 45 amps at 200 feet

Advertisement

45 A at 200 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper2 AWG3.49 V (2.91%)
120 VAluminum2/0 AWG2.86 V (2.38%)
240 VCopper4 AWG5.54 V (2.31%)
240 VAluminum2 AWG5.74 V (2.39%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 45 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 45 amps at 200 feet?

At 240 V: 4 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath

Advertisement