WireMath

Home › Wire size by amps › 30 amp › 75 ft

Wire size for 30 amps at 75 feet

Advertisement

30 A at 75 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper8 AWG3.44 V (2.87%)
120 VAluminum4 AWG2.29 V (1.91%)
240 VCopper10 AWG5.45 V (2.27%)
240 VAluminum8 AWG5.67 V (2.36%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 30 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 30 amps at 75 feet?

At 240 V: 10 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath

Advertisement