WireMath

Home › Wire size by amps › 200 amp › 125 ft

Wire size for 200 amps at 125 feet

Advertisement

200 A at 125 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper4/0 AWG3.04 V (2.53%)
120 VAluminum300 kcmil3.54 V (2.95%)
240 VCopper3/0 AWG3.83 V (1.60%)
240 VAluminum250 kcmil4.24 V (1.76%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 200 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 200 amps at 125 feet?

At 240 V: 3/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances