Home › Wire size by amps › 90 amp › 75 ft

Wire size for 90 amps at 75 feet

Advertisement

90 A at 75 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper3 AWG3.31 V (2.76%)
120 VAluminum1 AWG3.42 V (2.85%)
240 VCopper3 AWG3.31 V (1.38%)
240 VAluminum2 AWG4.31 V (1.79%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 90 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 90 amps at 75 feet?

At 240 V: 3 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances