Wire size for 90 amps at 250 feet

Advertisement

90 A at 250 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper3/0 AWG3.45 V (2.87%)
120 VAluminum300 kcmil3.18 V (2.65%)
240 VCopper1 AWG6.93 V (2.89%)
240 VAluminum2/0 AWG7.16 V (2.98%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 90 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 90 amps at 250 feet?

At 240 V: 1 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances