WireMath

Home › Wire size by amps › 90 amp › 200 ft

Wire size for 90 amps at 200 feet

Advertisement

90 A at 200 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper2/0 AWG3.48 V (2.90%)
120 VAluminum250 kcmil3.05 V (2.54%)
240 VCopper2 AWG6.98 V (2.91%)
240 VAluminum2/0 AWG5.72 V (2.38%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 90 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 90 amps at 200 feet?

At 240 V: 2 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath

Advertisement