WireMath

Home › Wire size by amps › 110 amp › 300 ft

Wire size for 110 amps at 300 feet

Advertisement

110 A at 300 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper250 kcmil3.40 V (2.83%)
120 VAluminum400 kcmil3.49 V (2.91%)
240 VCopper2/0 AWG6.38 V (2.66%)
240 VAluminum4/0 AWG6.60 V (2.75%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 110 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 110 amps at 300 feet?

At 240 V: 2/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath