Home › Wire size by amps › 110 amp › 150 ft

Wire size for 110 amps at 150 feet

Advertisement

110 A at 150 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper2/0 AWG3.19 V (2.66%)
120 VAluminum4/0 AWG3.30 V (2.75%)
240 VCopper2 AWG6.40 V (2.67%)
240 VAluminum1/0 AWG6.63 V (2.76%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 110 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 110 amps at 150 feet?

At 240 V: 2 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances