Wire size for 110 amps at 125 feet

Advertisement

110 A at 125 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper1/0 AWG3.35 V (2.80%)
120 VAluminum3/0 AWG3.46 V (2.89%)
240 VCopper2 AWG5.33 V (2.22%)
240 VAluminum1/0 AWG5.53 V (2.30%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 110 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 110 amps at 125 feet?

At 240 V: 2 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances