14 AWG voltage drop at 250 feet

Computed voltage drop for 14 AWG copper conductors on a 250 ft one-way run.

18.42 V

drop on 14 AWG copper, 250 ft one-way, 12 A load · 15.4% of 120 V · 7.7% of 240 V

14 AWG at 250 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
3 A4.61 V3.8%1.9%OK
6 A9.21 V7.7%3.8%OK at 240 V up to 5%
9 A13.81 V11.5%5.8%Upsize
12 A18.42 V15.4%7.7%Upsize

Vd = 2 × length × R × I ÷ 1000, R = 3.07 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 200 ft · 300 ft

FAQ

What is the voltage drop on 14 AWG wire at 250 feet?

At 12 A (80% of its 15 A 75°C rating) 14 AWG copper drops 18.42 V over 250 ft one-way: 15.4% at 120 V or 7.7% at 240 V.

How far can I run 14 AWG at 12 amps?

To stay within 3% at 120 V, about 49 ft one-way; at 240 V about 98 ft.