WireMath

14 AWG voltage drop at 150 feet

Computed voltage drop for 14 AWG copper conductors on a 150 ft one-way run.

11.05 V

drop on 14 AWG copper, 150 ft one-way, 12 A load · 9.2% of 120 V · 4.6% of 240 V

14 AWG at 150 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
3 A2.76 V2.3%1.2%OK
6 A5.53 V4.6%2.3%OK
9 A8.29 V6.9%3.5%OK at 240 V up to 5%
12 A11.05 V9.2%4.6%OK at 240 V up to 5%

Vd = 2 × length × R × I ÷ 1000, R = 3.07 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 14 AWG wire at 150 feet?

At 12 A (80% of its 15 A 75°C rating) 14 AWG copper drops 11.05 V over 150 ft one-way: 9.2% at 120 V or 4.6% at 240 V.

How far can I run 14 AWG at 12 amps?

To stay within 3% at 120 V, about 49 ft one-way; at 240 V about 98 ft.