14 AWG voltage drop at 150 feet
Computed voltage drop for 14 AWG copper conductors on a 150 ft one-way run.
11.05 V
drop on 14 AWG copper, 150 ft one-way, 12 A load · 9.2% of 120 V · 4.6% of 240 V
14 AWG at 150 ft by load
| Load | Drop | % at 120 V | % at 240 V | 3% rule (240 V) |
|---|---|---|---|---|
| 3 A | 2.76 V | 2.3% | 1.2% | OK |
| 6 A | 5.53 V | 4.6% | 2.3% | OK |
| 9 A | 8.29 V | 6.9% | 3.5% | OK at 240 V up to 5% |
| 12 A | 11.05 V | 9.2% | 4.6% | OK at 240 V up to 5% |
Vd = 2 × length × R × I ÷ 1000, R = 3.07 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.
Same wire, other distances
25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 200 ft · 250 ft · 300 ft
FAQ
What is the voltage drop on 14 AWG wire at 150 feet?
At 12 A (80% of its 15 A 75°C rating) 14 AWG copper drops 11.05 V over 150 ft one-way: 9.2% at 120 V or 4.6% at 240 V.
How far can I run 14 AWG at 12 amps?
To stay within 3% at 120 V, about 49 ft one-way; at 240 V about 98 ft.