20 A

14 AWG copper at 75 °C · 15 A at 60 °C · 25 A at 90 °C

Voltage drop of 14 AWG copper

One-way10 A15 A20 A30 A50 A
25 ft1.53 V2.30 V3.07 V4.61 V7.67 V
50 ft3.07 V4.61 V6.14 V9.21 V15.35 V
100 ft6.14 V9.21 V12.28 V18.42 V30.70 V
150 ft9.21 V13.81 V18.42 V27.63 V46.05 V
200 ft12.28 V18.42 V24.56 V36.84 V61.40 V

Single-phase, DC resistance 3.07 Ω/1000 ft (Cu).

FAQ

How many amps can 14 AWG wire carry?

Copper 14 AWG: 15 A at 60 °C, 20 A at 75 °C, 25 A at 90 °C (breaker limited to 15 A by NEC 240.4(D)).