WireMath

12 AWG voltage drop at 75 feet

Computed voltage drop for 12 AWG copper conductors on a 75 ft one-way run.

4.63 V

drop on 12 AWG copper, 75 ft one-way, 16 A load · 3.9% of 120 V · 1.9% of 240 V

12 AWG at 75 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
4 A1.16 V1.0%0.5%OK
8 A2.32 V1.9%1.0%OK
12 A3.47 V2.9%1.4%OK
16 A4.63 V3.9%1.9%OK

Vd = 2 × length × R × I ÷ 1000, R = 1.93 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 100 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 12 AWG wire at 75 feet?

At 16 A (80% of its 20 A 75°C rating) 12 AWG copper drops 4.63 V over 75 ft one-way: 3.9% at 120 V or 1.9% at 240 V.

How far can I run 12 AWG at 16 amps?

To stay within 3% at 120 V, about 58 ft one-way; at 240 V about 117 ft.