12 AWG voltage drop at 100 feet

Computed voltage drop for 12 AWG copper conductors on a 100 ft one-way run.

6.18 V

drop on 12 AWG copper, 100 ft one-way, 16 A load · 5.1% of 120 V · 2.6% of 240 V

12 AWG at 100 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
4 A1.54 V1.3%0.6%OK
8 A3.09 V2.6%1.3%OK
12 A4.63 V3.9%1.9%OK
16 A6.18 V5.1%2.6%OK

Vd = 2 × length × R × I ÷ 1000, R = 1.93 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 12 AWG wire at 100 feet?

At 16 A (80% of its 20 A 75°C rating) 12 AWG copper drops 6.18 V over 100 ft one-way: 5.1% at 120 V or 2.6% at 240 V.

How far can I run 12 AWG at 16 amps?

To stay within 3% at 120 V, about 58 ft one-way; at 240 V about 117 ft.