12 AWG voltage drop at 150 feet

Computed voltage drop for 12 AWG copper conductors on a 150 ft one-way run.

9.26 V

drop on 12 AWG copper, 150 ft one-way, 16 A load · 7.7% of 120 V · 3.9% of 240 V

12 AWG at 150 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
4 A2.32 V1.9%1.0%OK
8 A4.63 V3.9%1.9%OK
12 A6.95 V5.8%2.9%OK
16 A9.26 V7.7%3.9%OK at 240 V up to 5%

Vd = 2 × length × R × I ÷ 1000, R = 1.93 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 12 AWG wire at 150 feet?

At 16 A (80% of its 20 A 75°C rating) 12 AWG copper drops 9.26 V over 150 ft one-way: 7.7% at 120 V or 3.9% at 240 V.

How far can I run 12 AWG at 16 amps?

To stay within 3% at 120 V, about 58 ft one-way; at 240 V about 117 ft.