12 AWG voltage drop at 150 feet
Computed voltage drop for 12 AWG copper conductors on a 150 ft one-way run.
9.26 V
drop on 12 AWG copper, 150 ft one-way, 16 A load · 7.7% of 120 V · 3.9% of 240 V
12 AWG at 150 ft by load
| Load | Drop | % at 120 V | % at 240 V | 3% rule (240 V) |
|---|---|---|---|---|
| 4 A | 2.32 V | 1.9% | 1.0% | OK |
| 8 A | 4.63 V | 3.9% | 1.9% | OK |
| 12 A | 6.95 V | 5.8% | 2.9% | OK |
| 16 A | 9.26 V | 7.7% | 3.9% | OK at 240 V up to 5% |
Vd = 2 × length × R × I ÷ 1000, R = 1.93 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.
Same wire, other distances
25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 200 ft · 250 ft · 300 ft
FAQ
What is the voltage drop on 12 AWG wire at 150 feet?
At 16 A (80% of its 20 A 75°C rating) 12 AWG copper drops 9.26 V over 150 ft one-way: 7.7% at 120 V or 3.9% at 240 V.
How far can I run 12 AWG at 16 amps?
To stay within 3% at 120 V, about 58 ft one-way; at 240 V about 117 ft.