WireMath

Home › Ampacity chart › 12 AWG

12 AWG wire specs

Advertisement
25 A

12 AWG copper at 75 °C · 20 A at 60 °C · 30 A at 90 °C · aluminum 20 A at 75 °C

Voltage drop of 12 AWG copper

One-way10 A15 A20 A30 A50 A
25 ft0.96 V1.45 V1.93 V2.90 V4.83 V
50 ft1.93 V2.90 V3.86 V5.79 V9.65 V
100 ft3.86 V5.79 V7.72 V11.58 V19.30 V
150 ft5.79 V8.69 V11.58 V17.37 V28.95 V
200 ft7.72 V11.58 V15.44 V23.16 V38.60 V

Single-phase, DC resistance 1.93 Ω/1000 ft (Cu) / 3.18 Ω (Al).

FAQ

How many amps can 12 AWG wire carry?

Copper 12 AWG: 20 A at 60 °C, 25 A at 75 °C, 30 A at 90 °C (breaker limited to 20 A by NEC 240.4(D)).