Box Fill Calculator

Calculate the required electrical box volume from conductors, devices, clamps and grounds using NEC 314.16 volume allowances.

Advertisement

How to use it

  1. Count each insulated conductor that enters and terminates or splices in the box (pigtails that stay inside are not counted).
  2. Each device counts as 2 conductors of the largest size connected to it.
  3. All clamps together count as 1; all grounds together count as 1.

How it works

Required volume = (conductors + 2 × devices + clamps + grounds) × the allowance for the largest conductor (NEC Table 314.16(B)).

FAQ

How many wires can go in a single gang box?

An 18 in³ plastic box holds 9 × 14 AWG or 8 × 12 AWG allowances in total.