WireMath

Home › Wire size by amps › 70 amp › 300 ft

Wire size for 70 amps at 300 feet

Advertisement

70 A at 300 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper3/0 AWG3.22 V (2.68%)
120 VAluminum250 kcmil3.56 V (2.96%)
240 VCopper1 AWG6.47 V (2.69%)
240 VAluminum2/0 AWG6.68 V (2.78%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 70 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 70 amps at 300 feet?

At 240 V: 1 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn

Free calculator by WireMath

Advertisement