Wire size for 70 amps at 200 feet

Advertisement

70 A at 200 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper1/0 AWG3.42 V (2.85%)
120 VAluminum3/0 AWG3.53 V (2.94%)
240 VCopper3 AWG6.86 V (2.86%)
240 VAluminum1 AWG7.08 V (2.95%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 70 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 70 amps at 200 feet?

At 240 V: 3 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.