Home › Wire size by amps › 400 amp › 25 ft

Wire size for 400 amps at 25 feet

Advertisement

400 A at 25 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper600 kcmil0.43 V (0.36%)
120 VAluminum>600 kcmil–
240 VCopper600 kcmil0.43 V (0.18%)
240 VAluminum>600 kcmil–

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 400 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 400 amps at 25 feet?

At 240 V: 600 kcmil copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances

Advertisement
XFacebookRedditWhatsAppLinkedIn